9482 6 031 001 1
3 of 4
2016
03.03. Bagusch
Kaiser
Temperature Input Module
Type 9482/32-08-1*
01 09.03.2018 Bagusch
Grounded RTD or potentiometer connected in a mixed configuration with Vi
For connection of up to 8 passive I.S. circuits. Thermocouples and external CJC circuit might also be connected, their calculation is below.
Calculated with the following maximum values:
2-Wire:
Connector X1 / X2
– Channel 0 (1/4); Channel 1 (5/8) up to Channel 7 (29/32)
Input
Voc = 6.42 V
Vi = 6.5 V
Voc ext = 12.92 V
Isc = 47.9 mA
P
o
= 155 mW
3-Wire:
Connector X1 / X2
– Channel 0 (1/3/4); Channel 1 (5/7/8); up to Channel 7 (29/31/32)
Input
Voc = 6.42 V
Vi = 6.5 V
Voc ext = 12.92 V
Isc = 58.5 mA
P
o
= 189 mW
4-Wire:
Connector X1 / X2
– Channel 0 (1/2/3/4); Channel 1 (4/6/7/8); up to Channel 7 (29/30/31/32)
Input
Voc = 6.42 V
Vi = 6.5 V
Voc ext = 12.92 V
Isc = 68.8 mA
P
o
= 222 mW
CL I, DIV 1, A,B / Zone 0, GP IIC
CL I, DIV 1, C-G / Zone 0, GP IIB/IIIC
L
a
[mH]
9
5
2
1
0.5
0.2
0.1
40
20
10
5
1
0.5
0.1
C
a
[µF]
0.23
0.31
0.41
0.50
0.60
0.76
0.93
0.94
1.3
1.6
1.9
2.9
3.4
5.6
2-Wire:
Connector X1 / X2
– Channel 0 (1/4); Channel 1 (5/8) up to Channel 7 (29/32)
Input
Voc = 6.42 V
Vi = 3.5 V
Voc ext = 9.92 V
Isc = 36.6 mA
P
o
= 91 mW
3-Wire:
Connector X1 / X2
– Channel 0 (1/3/4); Channel 1 (5/7/8); up to Channel 7 (29/31/32)
Input
Voc = 6.42 V
Vi = 3.5 V
Voc ext = 9.92 V
Isc = 44.8 mA
P
o
= 111 mW
4-Wire:
Connector X1 / X2
– Channel 0 (1/2/3/4); Channel 1 (4/6/7/8); up to Channel 7 (29/30/31/32)
Input
Voc = 6.42 V
Vi = 3.5 V
Voc ext = 9.92 V
Isc = 52.6 mA
P
o
= 131 mW
CL I, DIV 1, A,B / Zone 0, GP IIC
CL I, DIV 1, C-G / Zone 0, GP IIB/IIIC
L
a
[mH]
17
10
5
2
1
0.2
0.02
71
50
10
2
1
0.2
0.02
C
a
[µF]
0.34
0.46
0.58
0.74
0.78
1.3
2.8
1.4
1.8
2.9
4.2
4.9
7.8
20
Ungrounded Thermocouple and mV Sources in a mixed configuration with Vi
For connection of up to 8 passive or active, galvanically isolated and ungrounded I.S. circuits. RTD and potentiometer might also be connected,
their calculation is above. The external CJC might also be connected, the calculation is below. Calculated with the following maximum values:
Connector X1 / X2
– Channel 0 (2/3); Channel 1 (6/7) up to Channel 7 (30/31)
Input
Voc = 6.42 V
Vi = 6.5 V
Voc ext = 12.92 V
Isc = 6.53 mA
P
o
= 21.1 mW
CL I, DIV 1, A,B / Zone 0, GP IIC
CL I, DIV 1, C-G / Zone 0, GP IIB/IIIC
L
a
[mH]
100
50
10
5
1
0.5
0.2
100
50
10
1
0.5
0.2
0.1
C
a
[µF]
0.30
0.32
0.38
0.42
0.55
0.63
0.79
1.5
1.6
1.9
3.0
3.5
4.6
5.7
Grounded Thermocouple and mV Sources in a mixed configuration with Vi
For connection of up to 8 passive or active I.S. circuits. RTD and potentiometer might also be connected, their calculation is above. The external
CJC might also be connected, the calculation is below. Calculated with the following maximum values:
Connector X1 / X2
– Channel 0 (2/3); Channel 1 (6/7) up to Channel 7 (30/31)
Input
Voc = 6.42 V
Vi = 6.5 V
Voc ext = 12.92 V
Isc = 25 mA
P
o
= 81 mW
CL I, DIV 1, A,B / Zone 0, GP IIC
CL I, DIV 1, C-G / Zone 0, GP IIB/IIIC
L
a
[mH]
72
50
10
2
1
0.5
0.2
100
20
5
1
0.5
0.2
0.1
C
a
[µF]
0.17
0.22
0.34
0.46
0.53
0.62
0.78
1.2
1.6
2.1
3.0
3.5
4.5
5.7
Connector X1 / X2
– Channel 0 (2/3); Channel 1 (6/7) up to Channel 7 (30/31)
Input
Voc = 6.42 V
Vi = 3.5 V
Voc ext = 9.92 V
Isc = 19.2 mA
P
o
= 48 mW
CL I, DIV 1, A,B / Zone 0, GP IIC
CL I, DIV 1, C-G / Zone 0, GP IIB/IIIC
L
a
[mH]
100
50
10
2
1
0.2
0.02
100
20
5
1
0.5
0.1
0.02
C
a
[µF]
0.33
0.43
0.60
0.80
0.92
1.3
2.8
2.2
2.9
3.6
5.0
6
9.8
20