Temperature Input Module Zone 1
Series 9482/32
5
Technical Data
Explosion Protection
Global (IECEx)
Gas and dust
IECEx DEK 13.0046X
Ex ia [ia Ga] IIC T4 Gb
[Ex ia Da] IIIC
Europe (ATEX)
Gas and dust
DEKRA 13 ATEX 0140 X
E
II 2 (1) G Ex ia [ia Ga] IIC T4 Gb
E
II (1) D [Ex ia Da] IIIC
Certifications and certificates
Certificates
IECEx, ATEX, Brazil (INMETRO), India (PESO),
Canada (cFM), Kazakhstan (TR), Russia (TR),
Serbia (SRPS), USA (FM), Belarus (TR),
Ship approval
ABS, CCS, ClassNK, DNV GL, LR, RINA, RS
Further parameters
Installation
in Zone 1, Zone 2, Zone 21, Zone 22 and in the safe area
Further information
see respective certificate and operating instructions
Safety data
Note
See chapter "Documentation of intrinsic safety"
Max. internal capacity C
i
negligible
Max. internal inductance L
i
negligible
Technical Data
Electrical data
Ex i inputs
Resistance temperature
detector / resistance transmitter
Number of channels
8
Operating modes
8 channel precise/ 4 channel fast (joystick)
Connection type
2-, 3- and 4-wire circuits
Resistance range
0 to 10 kΩ
Measuring current
< 200 μA multiplexed
Max. line resistance per cable 100 Ω
Measurement accuracy
0.025 % (8 channel precise) / ± 1 % (4 channel fast joystick)
Note
All values in % of measuring range at 23 °C
Ambient temperature
influence
0.025 % / 10 K
Linearity (adjustable
parameters)
Temperature linear / resistance linear