Temperature Input Module Zone 1
Series 9482/32
6.2.2 Possible Types of Circuitry
Combination of connection A: only RTD, unearthed
17810E00
Up to 8 resistance temperature detectors or resistance transmitters
The following safety data are only applicable to
• circuitry with resistance temperature detectors and resistance
transmitters (combination of connection A)
• Circuitry with thermocouples and mV transmitters
(combinations of connection B – E)
• Circuitry combinations with resistance temperature detectors,
resistance transmitters and thermocouples and mV transmitters
(combinations of connection F – I)
Please note:
• The combinations of connections differ with respect to the specified
electrical safety measures (earthing, insulating) and the connected
reference junctions (internal, external) of the temperature sensors!
• The safety data for the thermocouples, resistance sensors and external
reference junctions must be determined separately in each case.
• Usually, the temperature sensors can be connected in any
configuration. Be sure to use the combinations of connections F – I
when connecting additional temperature or resistance sensors.
• An external reference junction may only be connected to channels 6
and 7.
Note
No thermocouples / mV transmitters connected, no reference junction
connected
Installation type
Insulated
Max. output voltage U
o ext
6.42 V
2-wire
3-wire
4-wire
Max. current I
o
6.5 mA
7.8 mA
9.8 mA
Max. power P
o
10.5 mW
12.5 mW
15.7 mW
Max. connectable
capacitance C
o
IIC
1.1
m
F
1.2
m
F
1.4
m
F
2.0
m
F
3.2
m
F
7.0
m
F
25
m
F
IIB / IIIC
5.8
m
F
6.3
m
F
7.1
m
F
10
m
F
19
m
F
51
m
F
570
m
F
Max. connectable
inductance L
o
IIC
100 mH
50 mH
20 mH
2 mH
0.2 mH
0.02 mH 0.002 mH
IIB / IIIC
100 mH
50 mH
20 mH
2 mH
0.2 mH
0.02 mH 0.002 mH