Temperature Input Module Zone 1
Series 9482/32
Thermocouples /
mV sensors
Number of
channels
8
Operating
modes
8 channel precise/4 channel fast
Connection
type
2-wire circuits
Signal range
-10 to +100 mV
Linearity
(adjustable
parameters)
Temperature linear / voltage linear
Note
All values in % of the measuring range at 23 °C
connectable
thermocouples /
mV sensors
Reaction time
Input resistance 10 MΩ
Ambient
temperature
influence
0.025 % / 10 K
Reference junction
compensation
Number of
channels
1 (clamping unit see operating instructions)
Operating
modes
internal (adjustable parameters) / external 3-wire circuit
Connection
type
3-wire circuit (external)
Measuring
range
-40 to +80 °C
Technical Data
Type
Reference
Measuring range
(ITS-90)
Medium
resolution
Medium error of
measurement
with regard to
measuring range
B
IEC 60584-1
+400 to +1800 °C
0.25 K
0.1%
E
IEC 60584-1
200 to +1000 °C
0.1 K
0.013%
J
IEC 60584-1
-200 to +1200 °C
0.1 K
0.014%
K
IEC 60584-1
-200 to +1370 °C
0.1 K
0.02%
N
IEC 60584-1
-200 to +1300 °C
0.1 K
0.02%
R
IEC 60584-1
-50 to +1767 °C
0.2 K
0.05%
S
IEC 60584-1
-50 to +1767 °C
0.2 K
0.053%
T
IEC 60584-1
-200 to +400 °C
0.1 K
0.042%
L
DIN 43710
-200 to +900 °C
0.1 K
0.027%
U
DIN 43710
-200 to +600 °C
0.1 K
0.038%
XK
GOST 8.585
-50 to +800 °C
0.1 K
0.02%
mV
–
0 to +100 mV
3.6 μV
0.01%
Type
Type of
connection
Operating mode
4 channel fast
Error control
Operating mode
8 channel accurate
Error control
Activated
Deactivated Activated
Deactivated
Thermoco
uple
2-wire
500 ms
450 ms
800 ms
750 ms
0 to
100 mV
2-wire
500 ms
450 ms
800 ms
750 ms
To achieve the times with "error control deactivated", the error control must be
"OFF" for all channels! As soon as the error control is "ON" for just one
channel, the times for "error control activated" apply.