The following conditions must be observed during project engineering:
• To ensure adherence with the intended use, only install the device on the
9494 IS1 BusRail.
• Operation of the device is only permissible in three approved mounting positions
(see the "Mounting/dismounting on BusRail" chapter).
• Modules with intrinsically safe and non-intrinsically safe field circuits may be operated
simultaneously on one BusRail.
6.1
Terminal Assignment
For the module, two pluggable terminals X1 and X2 (screw terminal 162702 or spring
clamp terminal 162695) for connection of field devices are available as accessories
(not included in the scope of delivery of the module). The pluggable terminals have
16 clamping units for connection of the field cables.
Terminal assignment of the pluggable terminals X1 and X2
Resistance sensors
Thermocouples and
mV transmitters
External reference junction
16495E00
16552E00
16551E00
2-wire
3-wire
4-wire
2-wire
3-wire
Chan-
nel
X1/X2 terminals
X1/X2 terminals
X2 terminals
0
1 (I+),
4 (I-)
1 (I+),
3 (V-),
4 (I-)
1 (I+),
2 (V+),
3 (V-),
4 (I-)
2 (V+), 3 (V-)
–
1
5 (I+),
8 (I-)
5 (I+),
7 (V-),
8 (I-)
5 (I+),
6 (V+),
7 (V-),
8 (I-)
6 (V+), 7 (V-)
–
2
9 (I+),
12 (I-)
9 (I+),
11 (V-),
12 (I-)
9 (I+),
10 (V+),
11 (V-),
12 (I-)
10 (V+), 11 (V-)
–
3
13 (I+),
16 (I-)
13 (I+),
15 (V-),
16 (I-)
13 (I+),
14 (V+),
15 (V-),
16 (I-)
14 (V+), 15 (V-)
–
4
17 (I+),
20 (I-)
17 (I+),
19 (V-),
20 (I-)
17 (I+),
18 (V+),
19 (V-),
20 (I-)
18 (V+), 19 (V-)
–
5
21 (I+),
24 (I-)
21 (I+),
23 (V-),
24 (I-)
21 (I+),
22 (V+),
23 (V-),
24 (I-)
22 (V+), 23 (V-)
–
6
25 (I+),
28 (I-)
25 (I+),
27 (V-),
28 (I-)
25 (I+),
26 (V+),
27 (V-),
28 (I-)
26 (V+), 27 (V-)
25 (I+)
7
29 (I+),
32 (I-)
29 (I+),
31 (V-),
32 (I-)
29 (I+),
30 (V+),
31 (V-),
32 (I-)
30 (V+), 31 (V-)
29 (I+), 32 (I-)