8.2.2 Dismounting / Replacement of the Module
• Loosen safety screws of the pluggable terminals X1 and X2.
• Pull out the terminals from the module.
• If necessary, remove the partition.
• Pull the blue notch lever of the module upwards to unlock the module.
• Remove the module vertically from the BusRail.
• Place the new module vertically on the BusRail and press it slightly to snap it into
place.
• The module may no longer be loosened without actuating the handle.
• If necessary, snap the partition into place between the modules.
• Plug the pluggable terminals X1 and X2 into the module and secure them against
loosening using screws (tightening torque 0.5 to 0.6 Nm).
Replacing older and other modules with 9482/32
Observe the following when replacing an IS1 module 9480/12 or 9481/12 with an
IS1+ module 9482/32 with the same functions:
• Ensure that the terminal assignment is adapted to that of the 9482/32.
• In order to use the new IS1+ functions, update the software of the CPM 9440 or
CPU 9441 if necessary.
• If necessary, use a new GSD in PROFIBUS-DP operation.
• Please contact your responsible distributor for further information.
DANGER
Explosion hazard due to impermissible module operating conditions!
Non-compliance results in severe or fatal injuries!
• Remove the terminals X1 and X2 from the module to be replaced
if a partition is mounted to guarantee a distance of 50 mm.
When replacing the module with a module with identical design, the set
parameters are maintained. No further user adjustments are necessary.
When replacing the module with a module with a different function,
the module reports a configuration error (red "ERR" LED flashes).
The module must be either re-configured or replaced with a module of
correct type.