IM-P309-02
MI Issue 2
74
16.1.1 Display of self-test errors (continued)
Display
(German)
Display
(English)
Description
Possible cause of
error and remedy
Parameter inkons.
params
inconsist
Parameter is
inconsistent.
Check the parameter
settings.
The set parameters
are contradictory.
Check the parameter
settings.
The set parameters
are contradictory.
Example: Upper-
range value, pulse
value and pulse
duration must be
matched in such
a way that the
combination fits for
all measured values.
ext EEPROM fehlt
missing
EEPROM
The data memory
module (DSM)
with the calibration
data of the sensor
and the customer-
specific settings of
the transmitter is not
plugged-in.
Insert the data
storage module
(DSM) in the socket
on the power supply
board UMF2-20.
Information:
Error message: "Parameter is inconsistent" (system error 0x0400)?
To generate a list of the inconsistencies, first enter a valid password and then
an invalid password. The control unit will show a list of current errors (only
once). The operator can then correct the inconsistent settings after entering a
valid password.