8.15 ELM sensor terminals
Sensor terminals
Terminal
Label
Polarity
Function
1
FE
Screen field coil
2
SP -
-
Field coil
3
SP +
+
Field coil
4
FE
Shield / Functional ground
5
E1
Elektrod 1
6
E2
Elektrod 2
8.16 Cable specification
If the transmitter is mounted separately from the sensor, the following cables must be used:
Electrode cable and field coil cable as shielded twisted pair. In order to protect the cable from
external interference, the twisted-pair wires are covered by an additional, overall shield e.g.
LIYCY-CY TP 2 x 2 x 0.25 mm².
At cable length more than 10m a wire cross section of at least 0.75 mm² is required e.g.
SLIYCY-C11Y ( 2 x ( 2 x 0.75 mm²)).
The outer shield is grounded by means of special EMC-compliant cable glands at both ends
of the cable.
Observe also the advice
in chapter 7 Environmental conditions.
FE
SP-
SP+
FE
E1
E2
1 2 3 4 5 6
Fig. 20