Chapter 2: Installation and Wiring
2-7
User’s Manual Pub. 0300246-01 Rev. C
To ensure optimum accuracy for voltage type outputs, limit overall cable
impedance by keeping all analog cables as short as possible. Locate the
I/O system as close to your voltage type sensors or actuators as possible.
Digital and analog power must be supplied by an Isolated Secondary
Limited Energy Low Voltage source.
Use Belden™ 8761, or equivalent, shielded wire.
WARNING
USE SUPPLY WIRES SUITABLE FOR 20 °C ABOVE
SURROUNDING AMBIENT TEMPERATURE.
WARNING
UTILISER DES FILS D’ALIMENTATION QUI CONVIENNENT A
UNE TEMPERATURE DE 20 °C AU-DESSUS DE LA
TEMPERATURE AMBIANTE.
Grounding
This product is intended to be mounted to a well-grounded mounting
surface such as a metal panel. Additional grounding connections from
the module’s mounting tabs or DIN rail (if used) are not required unless
the mounting surface cannot be grounded.
Under normal conditions, the drain wire (shield) should be connected to
the metal mounting panel (earth ground). Keep shield connection to earth
ground as short as possible.
Ground the shield drain wire at one end only. The typical location is at
the module end.
If it is necessary to connect the shield drain wire at the module end,
connect it to earth ground using a panel or DIN rail mounting screw.
Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-
Bradley publication 1770-4.1, for additional information.
Noise Prevention
Route field wiring away from any other wiring and as far as possible
from sources of electrical noise, such as motors, transformers, contactors,
and ac devices. As a general rule, allow at least 15.2 cm (6 in.) of
separation for every 120 V of power.
Routing field wiring in a grounded conduit can reduce electrical noise.
If field wiring must cross ac or power cables, ensure that they cross at
right angles.
If noise persists for a device, try grounding the opposite end of the cable
shield or ground both ends of the shield.
Содержание 1762sc-OF8
Страница 1: ......
Страница 6: ...vi MicroLogix 1200 8 Ch Output Module User s Manual Pub 0300246 01 Rev C ...
Страница 33: ...Chapter 3 Configuring the 1762sc OF8 for RSLogix 500 3 13 User s Manual Pub 0300246 01 Rev C ...
Страница 38: ...A 4 Appendix A Specifications User s Manual Pub 0300246 01 Rev C ...
Страница 40: ...User s Manual Pub 0300246 01 Rev C ...
Страница 41: ...User s Manual Pub 0300246 01 Rev C ...