Chapter 3: Configuring the 1762sc-OF8 for RSLogix 500
3-9
User’s Manual Pub. 0300246-01 Rev. C
Table 3-5 (Input Data File)
Input Word Normal Run Mode
Command Mode
I:e.0
General Status Word 0
Command Echo
I:e.1
Output Status Word 1 (Ch 0-3) Response Code
I:e.2
Output Status Word 2 (Ch 4-7) Response Channel
I:e.3
Echo Config (Ch 0-1)
I:e.4
Echo Config (Ch 2-3)
I:e.5
Echo Config (Ch 4-5)
I:e.6
Echo Config (Ch 6-7)
I:e.7
Not Used
The following table describes each of the input data words when in command
mode.
Table 3-6 (Input Words - Command Mode)
Word
Description
Command Echo (Word 0)
Matches Command Word 0 (that is, O:e.0).
When this word matches the Command Word, it
indicates the command is complete. The
Response Code is now valid.
Response Code (Word 1)
Non-zero is an error (see Response Codes). This
is valid only when Command Echo matches
Command Word.
Response Channel (Word 2)
If Response Code error, indicates which
channel. Only applies to commands that involve
channels.
Echo of Data (Word 1)
Chan 1 Config
Chan 0 Config
Echo of Data (Word 2)
Chan 3 Config
Chan 2 Config
Echo of Data (Word 3)
Chan 5 Config
Chan 4 Config
Echo of Data (Word 4)
Chan 7 Config
Chan 6 Config
Not Used (Word 7)
Содержание 1762sc-OF8
Страница 1: ......
Страница 6: ...vi MicroLogix 1200 8 Ch Output Module User s Manual Pub 0300246 01 Rev C ...
Страница 33: ...Chapter 3 Configuring the 1762sc OF8 for RSLogix 500 3 13 User s Manual Pub 0300246 01 Rev C ...
Страница 38: ...A 4 Appendix A Specifications User s Manual Pub 0300246 01 Rev C ...
Страница 40: ...User s Manual Pub 0300246 01 Rev C ...
Страница 41: ...User s Manual Pub 0300246 01 Rev C ...