Chapter 3: Configuring the 1762sc-OF8 for RSLogix 50
User’s Manual Pub. 0300246-01 Rev. C
Table 3-7 (Response Codes)
Name
Value
Description
Success
0×0000 The command was completed successfully.
Invalid
Command
0×F001 An invalid command code was issued.
Locked
0×F002
A command was issued before the Unlock was
given.
Invalid State
0×F003
One or more Fixed Words invalid. The module
will remain in its previous state until all of the
words are set correctly.
Invalid Config
0×F004
A configuration for one of the channels is
invalid. Check Response Channel to determine
which one. First error detected is displayed.
No Config
0×F005
An attempt was made to exit Command Mode
before a configuration was loaded. Either load
the default config or manually enter a
configuration for all channels.
Invalid Cal
0×F006
Calibration is invalid. Module requires factory
calibration before it can be configured.
NOTE
Response codes are not to be considered valid until the Command Echo
matches the issued command.
NOTE
Response codes will remain valid after the Exit command until the timeout
expires. After that, normal Input File operation takes over. Words 0-2 are
status.
3.5.2
Input Data File (Normal Run Mode)
In normal run mode, the input data file displays general module status, channel
status, and an echo of each channel configuration.
Use the addressing scheme in Figure 3-3 to locate the 8 input words.
Содержание 1762sc-OF8
Страница 1: ......
Страница 6: ...vi MicroLogix 1200 8 Ch Output Module User s Manual Pub 0300246 01 Rev C ...
Страница 33: ...Chapter 3 Configuring the 1762sc OF8 for RSLogix 500 3 13 User s Manual Pub 0300246 01 Rev C ...
Страница 38: ...A 4 Appendix A Specifications User s Manual Pub 0300246 01 Rev C ...
Страница 40: ...User s Manual Pub 0300246 01 Rev C ...
Страница 41: ...User s Manual Pub 0300246 01 Rev C ...