3-8
Chapter 3: Configuring the 1762sc-OF8 for RSLogix 50
User’s Manual Pub. 0300246-01 Rev. C
Output Range Output Value Condition
Raw/Prop EU
PID
% FS
0.00 VDC
Low Limit
-32768
0
0
0
1 to 5V
5.50 VDC
High Limit
32767
5500
18431 11250
5.00 VDC
High Range
26809
5000
16383 10000
1.00 VDC
Low Range
-20853
1000
0
0
0.00 VDC
Low Limit
-32768
000
-4096
-2500
3.4.2
Output Data File (Normal Run Mode)
The output data file is used to configure each channel for the OF8 as well as
control the output signal of each channel. Use the addressing scheme shown in
Figure 3-2 above.
In normal run mode, output words 0 through 7 control the analog output signal
for channels 0 through 7 respectively. See Table 3-1 above.
Section 3.5
Module Status
Input data for the OF8 consists of status information, channel configuration
information and module configuration status.
3.5.1
Input Data File (Command Mode)
In command mode, the input data file returns module configuration status used
during the configuration process. Refer to section 3.4.1 for more information
regarding command mode. Use the addressing scheme below to locate the 8
input words.
Figure 3-3 (Input Addressing Scheme)
1.
I/O located on the controller (embedded I/O) is slot 0. I/O added to the
controller (expansion I/O) begins with slot 1.
The layout for the input data file is shown below.
Содержание 1762sc-OF8
Страница 1: ......
Страница 6: ...vi MicroLogix 1200 8 Ch Output Module User s Manual Pub 0300246 01 Rev C ...
Страница 33: ...Chapter 3 Configuring the 1762sc OF8 for RSLogix 500 3 13 User s Manual Pub 0300246 01 Rev C ...
Страница 38: ...A 4 Appendix A Specifications User s Manual Pub 0300246 01 Rev C ...
Страница 40: ...User s Manual Pub 0300246 01 Rev C ...
Страница 41: ...User s Manual Pub 0300246 01 Rev C ...