2-6
Chapter 2: Installation and Wiring
User’s Manual Pub. 0300246-01 Rev. C
Section 2.5
System
Assembly
The expansion I/O module is attached to the controller or another I/O module by
means of a ribbon cable
after
mounting as shown below.
Figure 2-4
NOTE
Use the pull loop on the connector to disconnect modules. Do not pull on
the ribbon cable.
WARNING
EXPLOSION HAZARD
In Class I, Division 2 applications, the bus connector must be fully
seated and the bus connector cover must be snapped in place.
In Class I, Division 2 applications, all modules must be mounted
in direct contact with each other as shown in the graphic. If DIN
rail mounting is used, an end stop must be installed ahead of the
controller, and after the last 1762 I/O module.
Section 2.6
Field Wiring
Connections
Consider the following when wiring your system:
General
Power and output wiring must be in accordance with Class 1, Division 2
wiring methods, Article 501-4(b) of the National Electric Code, NFPA
70, and in accordance with the authority having jurisdiction.
The analog common (COM) is not connected to earth ground inside the
module. All terminals are electrically isolated from the system.
Содержание 1762sc-OF8
Страница 1: ......
Страница 6: ...vi MicroLogix 1200 8 Ch Output Module User s Manual Pub 0300246 01 Rev C ...
Страница 33: ...Chapter 3 Configuring the 1762sc OF8 for RSLogix 500 3 13 User s Manual Pub 0300246 01 Rev C ...
Страница 38: ...A 4 Appendix A Specifications User s Manual Pub 0300246 01 Rev C ...
Страница 40: ...User s Manual Pub 0300246 01 Rev C ...
Страница 41: ...User s Manual Pub 0300246 01 Rev C ...