A-2
Appendix A: Specifications
User’s Manual Pub. 0300246-01 Rev. C
Specification
Value
Isolation
Channel to Rack
707 VDC for 1 minute (withstand voltage)
Channel to Channel
Return lines are connected together. No isolation
between channels.
Module Power LED
On: indicates power is applied and module not faulted.
See Section 1.4.1 for more information.
Vendor I.D.
58
Product Type
10
Product Code
21
Agency Certification
C-UL listed (under CSA C22.2 No. 142) UL 508 listed
CE compliant for all applicable directives
Hazardous Environment
Class
Class I, Division 2, Hazardous Location, Groups A, B,
C, D (ISA 12.12.01, C-UL under CSA C22.2 No. 213)
Operating Temperature Code T6
Radiated and
Conducted Emissions
EN61131-2
Electrical /EMC:
The module has passed testing at the following levels:
ESD Immunity
(IEC61000-4-2)
4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity
(IEC61000-4-3)
10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed carrier
Fast Transient Burst
(IEC61000-4-4)
2 kV, 5 kHz
Surge Immunity
(IEC61000-4-5)
1 kV galvanic gun
Conducted Immunity
(IEC61000-4-6)
10 V, 0.15 to 80 MHz
8
8
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency
range is 30 MHz to 2700 MHz.
Содержание 1762sc-OF8
Страница 1: ......
Страница 6: ...vi MicroLogix 1200 8 Ch Output Module User s Manual Pub 0300246 01 Rev C ...
Страница 33: ...Chapter 3 Configuring the 1762sc OF8 for RSLogix 500 3 13 User s Manual Pub 0300246 01 Rev C ...
Страница 38: ...A 4 Appendix A Specifications User s Manual Pub 0300246 01 Rev C ...
Страница 40: ...User s Manual Pub 0300246 01 Rev C ...