Section 3: Operation
Page 3-24
NetClock/GTP Instruction Manual
For cable runs less than 1500 feet, a lower-cost twisted pair cable may be used.
Refer to Table 3-6 for possible sources.
MANUFACTURER
PART NUMBER
Alpha Wire Corporation
1-800-52ALPHA
5471
Belden Wire and Cable Company
1-800-BELDEN-1
9501
Carol Cable Company
606-572-8000
C0600
TABLE 3-6 CABLE SOURCES FOR RS-485 LINES UNDER 1500 FEET
3.4.2 Connection
Method
The RS-485 transmission line must be connected in a daisy chain configuration
as shown in Figure 3-8. In a daisy chain configuration, the transmission line
connects from one RS-485 receiver to the next. The transmission line appears
as one continuous line to the RS-485 driver.
A branched or star configuration is not recommended. This method of
connection appears as stubs to the RS-485 transmission line. Stub lengths
affect the bus impedance and capacitive loading which could result in reflections
and signal distortion.
FIGURE 3-8 ONE-WAY BUS INSTALLATION
Содержание 8183A GTP
Страница 36: ...Section 3 Operation Page 3 2 NetClock GTP Instruction Manual FIGURE 3 1 NETCLOCK GTP FRONT PANEL...
Страница 39: ...Section 3 Operation NetClock GTP Instruction Manual Page 3 5 FIGURE 3 2 NETCLOCK GTP REAR PANEL...
Страница 64: ...SECTION 4 SOFTWARE COMMANDS 4 0 INTRODUCTION 4 1 4 22 RS 232 COMMAND SET...
Страница 96: ...SECTION 5 SERVICE INFORMATION 5 0 INTRODUCTION 5 1 RECEPTION TROUBLESHOOTING 5 2 TCXO ADJUSTMENT...
Страница 102: ...APPENDIX A IRIG CODE DESCRIPTION A 0 INTRODUCTION A 1 FAA IRIG B CODE...
Страница 104: ...Appendix A FAA IRIG Code Description Page A 2 NetClock GTP Instruction Manual FIGURE A 1 FAA IRIG B TIME CODE...