Initial charge
6
.
1
.
1 Initial charge should be conducted for batteries that have never been used
6
.
2 Use and maintenance
6
.
2
.
1 In order to guarantee the service life of the batteries, the batteries in use should be fully charged.
Insufficiently charged batteries must not be used. During the process of use, close attention should be paid to
the discharge extent. Over discharge is prohibited.
6
.
2
.
2The batteries in normal use should avoid over-charge, but over-charge must be properly conducted for
the batteries in following situations, i.e. equalizing charge.
a. The “lag
-
behind” batteries
--- batteries with a voltage lower than that of the other batteries in the
discharging process and the batteries having been repaired for failure. (When equalizing charge is
conducted, the positive and negative poles of the “lag
-
behind” battery should be respectively
connected with the positive and negative ends of the charger, the DC power supply, and the charge
should be conducted independently.)
b. Equalizing charge should be conducted for the batteries in normal use every 2-3 months.
c. Equalizing charge should be conducted for the batteries that have not been used for a long period of
time before use.
6
.
3 Storage
Batteries should be stored in a clean, dry and well ventilated warehouse with a temperature of 5-40
℃
. The
valid shelf life is 2 years. The batteries should be kept according to the following requirements during storage:
a.
No direct sunshine on the batteries and at least 2m away from heat source.
b.
Avoid contacting with any harmful substances. No metallic matters are allowed to drop into the
batteries.
c.
The batteries should not be placed upright down and should not be impacted mechanically or
heavily compressed.
The batteries must not be stored with electrolytic solution. When it is required in special situation that the
batteries must be stored with electrolytic solution, the batteries should be fully charged and the density
and the liquid surface of the electrolytic solution should be adjusted to the stipulated values. When the
storage period comes to one month, the batteries should be complementarily charged with the
common charge method.
6
.
4 Charger
If the charger you use is full automatic type. It must meet with the following 2 requirements:
a. The output voltage of charger: 24V
b. The output current of charger: 30A
Warning
There is
hydrogen gas accumulated in the battery case during
charging.
Thus the charging environment requires good ventilation and
there should be no flame, otherwise explosion or fire may occur.