12. Special functions
Menu “7. Special functions” is used
to set basic items and expanded
functions.
The menu is closed by pressing
“esc” or selecting “Exit special func-
tions”.
12.1 Program selections
menu 7.1
The suitable hydraulic variant for the specific application is selected and
set here (see 2.5 Hydraulic variants). The associated diagram can be
displayed by pressing “info”.
Setting range: 1-15/default setting: 1
Caution
12.2 Time & date
menu 7.2
This menu is used to set the current time and date.
Caution
Normally the program selection is made only once during initial
commissioning by the specialist. Incorrect program selection can
lead to unpredictable errors.
For analysis of the system data it is essential for the time to be
set accurately on the controller. Please note that the clock does not
continue to run if the mains voltage is interrupted, and must therefore
be reset.
Caution
12.3 Sensor calibration
menus 7.3 / 7.3.1 - 7.3.3
Deviations in the temperature values displayed, for example due to cables
which are to long or sensors which are not positioned optimally, can be
compensated for manually here. The settings can be made for each indi-
vidual sensor in steps of 0.5°C.
Offset S1...S6 per setting range: -50°C...+50°C default setting: 0°C
Caution
Settings are only necessary in special cases at the time of initial
commissioning by the specialist. Incorrect measurement values
can lead to unpredictable errors.
Other than the time all set-
tings may only be made by
a specialist.