33
10. Settings
Settings
menu 5
10
10
Caution
Caution
This does not under any
circumstances replace
the safety facilities to be
provided by the customer!
The menu is closed by pressing
“esc” or selecting “Exit settings”.
Various settings can be made depending on the selection of
hydraulic variant 1-15. This is explained in more detail in Table
10.14. This table also indicates the associated reference sensors
and switch outputs. The following pages contain generally valid
descriptions for the settings.
The necessary basic settings
required for the control function are
made in menu “5. Settings”.
10.1 Tmin S1
menu 5.x
= enable/start temperature at sensor 1
If this value is exceeded at sensor 1 and the other conditions are also met,
then the controller switches the associated pump and/or valve on. If the
temperature at sensor 1 drops below this value by 5°C, then the pump
and/or the valve are switched off again.
Setting range: from 0°C to 99°C/default setting: 20°C
10.2 Tmin S2
menu 5.x
= enable/start temperature at sensor 2
If this value is exceeded at sensor 2 and the other conditions are also met,
then the controller switches the associated pump and/or valve on. If the
temperature at sensor 2 drops below this value by 5°C, then the pump
and/or the valve are switched off again.
Setting range: from 0°C to 99°C/default setting: 40°C
10.3 Tmin S3
menu 5.x
= enable/start temperature at sensor 3
If this value is exceeded at sensor 3 and the other conditions are also met,
then the controller switches the associated pump and/or valve on. If the
temperature at sensor 3 drops below this value by 5°C, then the pump
and/or the valve are switched off again.
Setting range: from 0°C to 99°C/default setting: 20°C