27
Room controller
This menu is used to determine the settings for the room controller RC22. The menu is
closed by pressing “esc” or selecting “Exit room controller”.
5.5. - Room controller
This menu is used to determine the in
fl
uence the room temperature has on the refer-
ence
fl
ow temperature in heating mode. For every degree of difference between room
temperature and reference room temperature the percentage set here is added to
resp. subtracted from the calculated reference
fl
ow temperature. Limits like Min
fl
ow
heating and Max
fl
ow heating do apply.
Example
: Reference room temp.: 25 °C ; room temp.: 20 °C = 5 °C Difference.
Room reference.: e.g. 40 °C : Room controller: 10 % = 4 °C
5 X 4 °C = 20 °C Result: 20 °C are added to the reference
fl
ow temp. =60 °C.
If Max.
fl
ow is below 60°, the result is equal to Max.
fl
ow.
Settings range: 0 % to 20 % / Default: 0
5.5.1. - Infl uence room temperature
Caution
The room controller is not used in the operating modes „Reference value“ and
„14 days reference.
Caution
The RC22 is used to set the 3 operating modes Heating, Off and Cool-
ing. Also the dial is used to in
fl
uence the reference
fl
ow temperature
(heating) respectively the reference room temperature (cooling) by paral-
lel translating the charakteristik curve.
Room reference temperature during day time operation
The desired room temperature in day mode. As long as this condition is not met, the
reference
fl
ow temperature is raised resp. lopwered, depending on the value set in
menu „5.5.1. - In
fl
uence room temperature“. When “in
fl
uence room temperature” is set
0%, this settings is without effect.
Settings range: 10° C to 30° C / Default: 20° C
5.5.2. - Room ref. day
Room reference temperature during night time operation
The desired room temperature in night mode. As long as this condition is not met, the
reference
fl
ow temperature is raised resp. lopwered, depending on the value set in
menu „5.5.1. - In
fl
uence room temperature“. When “in
fl
uence room temperature” is set
0%, this settings is without effect.
Settings range: 10° C to 30° C / Default: 20° C
5.5.3. - Room ref. night