10
Installation
The temperature sensor cables must be routed separately from mains
voltage cables, and must not, for example, be routed in the same cable
duct!
The controller operates with Pt1000 temperature sensors which are accurate to the
degree, thus ensuring optimal control of system functions.
Caution
Caution
If needed the sensor cables can be extended to a maximum of 30m
using a cable with a cross-section of at least 0.75mm². Make sure that
there is no contact resistance!
Position the sensor precisely in the area to be measured!
Only use immersion, pipe-mounted or
fl
at-mounted sensor suitable for
the speci
fi
c area of application with the appropriate permissible tem-
perature range.
C.3. - Installing temperature sensors