19
Operating modes
Summer
= Dehumdi
fi
er is active when the temperature set in S/W day resp. S/W night
is exceeded.
All year
= Dehumidi
fi
er tries to keep the humidity level all time.
Off
= Dehumidi
fi
er switched off
Settings range: Summer, All year, Off
Default: Off
4.3. - Dehumidifi er
Operating manual mode:
The relays and thus the connected consumer are switched on and off by pressing a
key, with no regard to the current temperatures and the parameters which have been
set.
In Manual mode the individual relay outputs and the connected consumers can be
checked for proper functioning and correct assignment.
4.4. - Manual
The operating mode “Manual” may only be used by specialists for brief
function tests, e.g. during commissioning!
Danger
If operating mode “Reference value” is selected in „4.1. - Heating circuit“ , the refer-
ence
fl
ow temperature has to be set here, regardless of the curve/outdoor tempera-
ture.
Settings range: 10 °C to 75 °C
Default: 30 °C
4.5. - Heat circuit reference
If operating mode “14 day reference value” is selected, see „4.1. - Heating circuit“, the
reference
fl
ow temperature for each of the 14 days can be set here.
In the
fi
rst menu 4.6.1 the starting time of the program is shown. To start the program,
hit restart, and the current time is the new starting time.
Hitting “restart” again will reset the 14 day reference program and start it at day 1.
4.6. - 14 day reference