animeo KNX 4 AC MoCo · REF. 5071074 -
10/47
Communication objects
At the most, 150 communication objects are available for use, but not all at once. A maximum of 250 group addresses can be connected.
5
No. Object name
Model
DPT_ID
Description
1
Motor 1 UP / DOWN, CLOSED / OPEN
1 Bit
1.001
If a telegram with the value "0" is received by this communication
object, the corresponding blind is moved upwards or a window
is closed. If a telegram with the value "1" is received, the corre-
sponding blind is moved down or a window is opened. At the end
of the set move time for UP or DOWN direction or the move time for
opening or closing of the window, the relays of the outputs are
freed.
2
Motor 2 UP / DOWN, CLOSED / OPEN
1 Bit
1.001
3
Motor 3 UP / DOWN, CLOSED / OPEN
1 Bit
1.001
4
Motor 4 UP / DOWN, CLOSED / OPEN
1 Bit
1.001
5
Motor 1 STEP / STOP
1 Bit
1.001
With Venetian blinds:
If the Venetian blind is moving, the move is
stopped with the receiving of a telegram on one of these commu-
nication objects, no matter whether "0" or "1" is received. If the
Venetian blind is stationary, a turn is carried out. In addition, the
slats turn CLOSED with the receiving of a telegram with the value
"1" and UP with the receiving of a telegram with the value "0". The
duration of the turning step is defined in the parameter settings.
With vertical awnings, roller shutters, awnings and windows:
When one of the end products is moving, the move is stopped with
the receiving of a telegram on one of these communication objects,
no matter whether "0" or "1" is received. If one of these end
products is not moving and a telegram is received on one of these
communication objects, then no operation is carried out.
6
Motor 2 STEP / STOP
1 Bit
1.001
7
Motor 3 STEP / STOP
1 Bit
1.001
8
Motor 4 STEP / STOP
1 Bit
1.001
9
Motor 1 Position UP / DOWN
1 Byte
5.004
If a telegram is received on one of these communication objects, the
corresponding blind will move to the position which is defined by
the received value "0" = upper / "255" = lower.
With Venetian blinds:
When the position is reached, the same
slats angle is moved to at which the Venetian blind was before.
Between the receiving of a telegram on the objects 9-12 and the receiving of a telegram on
the objects 13-16, a temporary time lapse of 2 seconds must be taken into consideration.
10
Motor 2 Position UP / DOWN
1 Byte
5.004
11
Motor 3 Position UP / DOWN
1 Byte
5.004
12
Motor 4 Position UP / DOWN
1 Byte
5.004
13
Motor 1 Slat position
1 Byte
5.004
With Venetian blinds:
If a telegram is received on one of these
communication objects, the corresponding slats will move to the
position which is defined by the received value. If a Venetian blind
is moving and receives a value on the corresponding object, the
position of the slats is moved to only when the move has been
completed. Depending on the parameter settings on the card index
"General" the position is defined as follows:
"255" = slats max. closed /
value (0/255)
value (255/0)
"0" = slats max. turned
or
"0" = slats max. closed /
"255" = slats max. turned
14
Motor 2 Slat position
1 Byte
5.004
15
Motor 3 Slat position
1 Byte
5.004
16
Motor 4 Slat position
1 Byte
5.004
17
Motor 1 Move to IP 1
1 Bit
1.001
If a telegram with the value "1" is received on one of these com-
munication objects, the corresponding blind moves to the ETS
parametered per local switch, or to the radio hand-transmitted,
learned-in intermediate position 1. In addition, the learned-in
position is valid. With the receiving of a telegram with the value "0"
on one of these communication objects, the blinds 1-4 move to the
upper end position.
18
Motor 2 Move to IP 1
1 Bit
1.001
19
Motor 3 Move to IP 1
1 Bit
1.001
20
Motor 4 Move to IP 1
1 Bit
1.001
21
Motor 1-4 Move to IP 1
1 Bit
1.001
If a telegram with the value "1" is received on this communication
object, the blinds 1-4 move to the ETS parametered per local switch,
or to the radio hand-transmitted, learned-in intermediate position
1. In addition, the learned-in position is valid. With the receiving
of a telegram with the value "0" on this communication object, the
blinds 1-4 move to the upper end position.
22
Motor 1 Move to IP 2
1 Bit
1.001
If a telegram with the value "1" is received on one of these commu-
nication objects, the corresponding blind moves to the intermediate
position 2 parametered in the ETS parameters. With the receiving
of a telegram with the value "0" on one of these communication
objects, the corresponding blind moves to the upper end position.
23
Motor 3 Move to IP 2
1 Bit
1.001
24
Motor 3 Move to IP 2
1 Bit
1.001
25
Motor 4 Move to IP 2
1 Bit
1.001