animeo KNX 4 AC MoCo · REF. 5071074 -
22/47
Security position
Low priority
Selection options:
Upper end limit
Lower end limit
Intermediate position 1 (IP 1)
Intermediate position 2 (IP 2)
Ignore security
Stop
Close window
Open window
The "Security position low priority" for the corresponding blind is determined with this parameter. If a telegram with the value "1" is
received on one of these communication objects (objects 27-31) the corresponding blind moves to the position parametered in the ETS
parameters.
If a telegram with the value "0" is received on one of these communication objects, no operation is carried out.
If the function "Repeat last telegram after security" is set with "Yes" in the menu index card "Functions motor 1 ... 4”, the blind moves, after
ending of the "Low priority" (value "0"), again in the last position and angle before activation of this priority.
Security position
High priority
Selection options:
Upper end limit
Lower end limit
Ignore security
Stop
Close window
Open window
The "Security position high priority" for the corresponding blind is determined with this parameter. If a telegram with the value "1" is
received on one of these communication objects (objects 32-36), the corresponding blind moves to the position parametered in the ETS
parameters.
If a telegram with the value "0" is received on one of these communication objects, no operation is carried out.
If the function "Repeat last telegram after security" is set with "Yes" in the menu index card "Functions motor 1 ... 4”, it is checked whether
"Low priority" is active or inactive. When "Low priority" (value "1") is active the blinds move to the parametered "Security position low prior-
ity" (see previous point). If the "Low priority" (value "0") is also inactive, the blind moves again to the last position with the last angle before
activating the high and low priorities.
Cyclic monitoring time in seconds (0 - 255)
Selection options:
0
0 - 255 seconds
The cyclic monitoring time is active, as soon as a higher value than "0" is entered and refers to both security objects, low and high priority.
With active cyclic monitoring time, attention must be paid to the fact that the time of the cyclic transmitter is lower approx. 1/4 than
the parametered cyclic monitoring time for the security objects, low and high priority. If the predefined value
"0"
remains set, the security
objects react statically to the values "1" and "0".