Function /
parameter
Description
Unit / status
PFLM2
P(f) mode 2
-
PFLM2-STRTFQ
Start frequency
Hz
PFLM2-RDN
Reduction of active power
% of P
M
/Hz
PFLM2-RNC
Increase to rated output power
% of Pac nom/
min
Reactive power
Functions and parameters of the "Reactive power" sub-menu:
Function /
parameter
Description
Unit / status
QMO-AM
Reactive power control
0=OFF
QMCQ
Reactive power mode constant "Q"
-
QMCQ-QSV
Reactive power value
% of Pac nom
[OEX/UEX]
QMCQ-VLE
Status of the voltage-dependent reactive power
control hysteresis for QMCQ
Disabled/enabled
QMCQ-VLIH
Upper limit value of the mains voltage
V
QMCQ-VLOL
Lower limit value of the mains voltage
V
QMCQ-PLE
Status of the active power-dependent reactive
power control hysteresis for QMCQ
Disabled/enabled
QMCQ-PLI
Upper limit value of the active power
W
QMCQ-PLO
Lower limit value of the active power
W
QMCPP
Reactive power mode "cos
φ
(Pac)"
-
QMCPP-PSP1…PSP10 Characteristic values 1 to 10 of Pac active power
% of Pac nom
QMCPP-CPSP1…
CPSP10
Characteristic values 1 to 10 of power factor cos
φ
- [UEX/OEX]
QMCPP-VLE
Status of mains voltage-dependent reactive power
control hysteresis for QMCPP
Disabled/enabled
QMCPP-VLIH
Upper limit value of the mains voltage
V
QMCPP-VLOL
Lower limit value of the mains voltage
V
QMCCP
Reactive power mode "cos
φ
"
-
QMCCP-CPSV
cos
φ
value
- [UEX/OEX]
QMCCP-VLE
Status of mains voltage-dependent reactive power
control hysteresis for QMCCP
Disabled/enabled
QMCCP-VLIH
Upper limit value of the mains voltage
V
QMCCP-VLOL
Lower limit value of the mains voltage
V
QMCCP-PLE
Status of active power-dependent reactive power
control hysteresis for QMCCP
-
QMCCP-PLI
Upper limit value of the active power
W
QMCCP-PLO
Lower limit value of the active power
W
QMQU1
Reactive power mode "Q(Vac) mode 1"
-
QMQU1-VSP1 to VSP10 Characteristic values 1 to 10 of mains voltage (Vac) V