555 External power control
Via this interface the inverter can receive digital signals for the specification of the set-
point of active and reactive power. It is possible to connect ripple control receivers to this
interface.
The interface is configured with the free MaxTalk 2 Pro service software (see Section 12).
Figure 22 shows the connection of the ripple control receiver to the interface.
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
a
b
c
a
b
c
a
b
c
a
b
c
a
b
c
a
b
c
K6
K5
K4
K3
K2
K1
L
(230 V)
I max = 150 mA
N
I = 25 mA
N
K5
K6
K4
K3
K2
K1
NA
Ripple control receiver
Inverter
Figure 22 Connection diagram of ripple control receiver
Connection conditions
■
■
Max. 6 relay contacts can be connected
■
■
Max. input voltage: 230 V
AC
(phase)
■
■
Connectable cable diameters: min. 9.5 mm / max. 12.5 mm
■
■
Connectable conductor cross-sections: min. 0.25 mm
2
/ max. 2.5 mm
2
■
■
Input current: 25mA
■
■
Max. cable length: 200 m