Connecting the inverter to the mains
DANGER!
Fatal electric shock hazard!
■
■
Make sure the AC line is not live during connection work.
Connection conditions
■
■
Comply with the connecting conditions set by the grid operator in charge.
■
■
Connectable cable diameters: min. 9.5 mm / max. 12.5 mm
■
■
Permissible conductor cross-sections:
– flexible conductors (with or without ferrule) or rigid conductors: max. 16 mm
2
– flexible conductors with ferrules (with plastic sleeves): max. 10 mm
2
■
■
The AC input conductor must be fused. Minimum conductor cross sections and sug-
gested mains fuses:
Minimum conductor cross sections
SM4TP
SM5TP2
SM6TP2
SM7TP2
Phases L1, L2, L3
1.5 mm
2
1.5 mm
2
2.5 mm
2
2.5 mm
2
Neutral conductor N
Protective conductor PE
Recommended mains fuses
SM4TP
SM5TP2
SM6TP2
SM7TP2
Nominal current
10 A
10 A
13 A
13 A
Characteristics
C
C
C
C
■
■
Temperature resistance of the AC feed cable: ≥ 80 °C
■
■
Make sure the ambient temperatures for the mains fuses specified by the producer
are not exceeded.