en
43
Parameter
Description
Netmask
Specification of a subnet mask of the IP address.
TCP Port
Specification of the desired TCP port for Ethernet communication. Note: the
TCP port must be higher than 1023 (lower values are reserved for "Well Known
Services").
Note
You will find more details about data communication in the technical informa-
tion "MaxComm network". This document can be downloaded from our web-
site at:
www.solarmax.com/en/downloads/data-communication/maxcomm
.
6.3.3 Configuring the status signaling contact
The status signaling contact of the MCU is used for remote monitoring of the Compact
Station. Three settings are possible.
1. In the "Settings" menu, select the "Status relay" parameter.
2. Make the required setting:
Setting
Description
Off
The status signaling contact is always open.
Mains
When the Compact Station starts grid operation, the status signaling
contact of the MCU will close immediately and remains closed for as long
as the Compact Station is feeding in. After the unit disconnects from the
mains, the status signaling contact opens after expiry of the adjustable
delay.
Error
If a warning, failure or device error occurs, the status signaling contact of
the MCU closes after expiry of the adjustable delay (for error messages,
see Section 8.2). The status signaling contact is opens immediately when
the fault is no longer present.
3. Select the "
Status relay delay"
parameter and set the required delay:
Parameter
Description
Value range
Unit
Status relay del.
(status relay delay)
Delay time of status relay
0…99
s
6.3.4 Configuration of the PV generator monitoring
Monitoring the equipotential bonding kit
The potential equalization set (PAS) is an accessory component and serves to ground
the PV generator. The behavior of the inverter in the event of fuse failure in the potential
equalization set can be adjusted.
Содержание 330TS-SV Compact Station
Страница 3: ...en 3 en 3...
Страница 12: ...12 3 3 Dimensions Vorderansicht linke Seitenansicht Draufsicht Schnitt A A...
Страница 22: ...22 Installation plan Compact Station 1000 mm Ev 2 50 MN m2 Ev 2 20 MN m2 725 400 75 1 4 3 2 5 7 6...
Страница 27: ...en 27 25 mm M12 3 2 4 6 1 5 No Description 1 NH fuse circuit breaker...
Страница 83: ...en 83 Notes...