5 Electrical connection
DANGER!
Fatal electric shock hazard!
■
■
Make sure that the DC and AC supply cables are de-energized.
All cables are inserted through the watertight system cable pass-through elements.
5.1
Installing cable pass-through elements
Before installing the cable pass-through elements the cables have to be laid out and fixed
inside and outside the Compact Station. The cable pass-through elements do not include
a cable strain relief facility. Cable strain relief is achieved using the perforated or C rails
within the Compact Station.
Description
1 2
3
4
No.
Description
1
Cable
2
Shrink sleeve
3
Cover spigot (part of system cover)
4
Clamping nut (part of system cover)
Note
■
■
Any cable pass-through elements not used can be used as pressure-proof
reserve pass-through elements.
■
■
Any cable pass-through elements that have been opened and are used as
reserve elements must always be fitted with new covers (HSI 90-D).
■
■
Any dismantled or damaged covers must not be re-used!