9 DHW heating
i.e. the heating curve can include a sharp deflection or
bend.
Fig. 2-31_08_008_02sn
Adaptation of the 3-point heating curve (in
hea-
ting mode
)
i
Note the currently set temperature before you
change the values.
Current
outside tem-
perature
Perceived room
temperature
Recommended adap-
tation of heating curve
-15°C to -
5°C
too cold
Increase temperature
value at
7
too hot
Reduce temperature
value at
7
-5°C to
+5°C
too cold
Increase temperature
value at
11
too hot
Reduce temperature
value at
11
+5°C to
+15°C
too cold
Increase temperature
value at
8
too hot
Reduce temperature
value at
8
9 DHW heating
DHW can be heated up in two ways:
–
With a DHW tank: the energy source of the DHW
tank is the heating boiler or a buffer tank
1)
–
With a fresh water module: the energy source of
the fresh water module is the buffer tank
1)
1)
The upper layer area (=drinking water area) in the
buffer is reserved for supplying the DHW tank/fresh
water module.
9.1 DHW tank/drinking water area
Fig. 2-32_05-002-01
1 DHW tank temperature
2 Required DHW tank temperature
3 Temperature of the energy source (e.g. buffer
tank)
4 Info line: Charging requirement (Yes/No) to the
energy source.
5 DHW tank operating mode
6 DHW tank settings
7 Status line DHW tank
9.1.1 DHW tank settings
Fig. 2-33_16-076-02
1 Temperatures and hystereses
2 One-time charge
3 DHW tank operating mode
Temperatures and hystereses
1
Required temperature / hystereses 1
The DHW (or the drinking water area in the buffer tank)
is charged when required until the set
Required tem-
perature 1
is reached. A new charge starts when the
DHW tank temperature falls to the value
Required tem-
perature 1
less
Hysteresis
.
Operation manual
therminator II touch
25