Operation manual for the system operator
Read carefully before operating.
DR-0030-EN / v28-202109
Pellet boiler
pellet
elegance
Страница 1: ...Operation manual for the system operator Read carefully before operating DR 0030 EN v28 202109 Pellet boiler pelletelegance...
Страница 2: ...23 7 1 Domestic hot water tank 23 7 1 1 DHW tank settings 24 7 2 Fresh water module FWM optional 24 8 Recirculation control 25 8 1 Circulation settings 25 8 2 Recirculation control Options 26 9 Buffe...
Страница 3: ...el The work procedures described in this manual must only be carried out by qualified specialist per sonnel Work on electrical components must only be per formed by trained electricians and in accorda...
Страница 4: ...ely Expansion tank prevents air suction when the system cools down Correctly set the pres sure check it regularly Existing underfloor heating Take care with old diffusion open plastic pipes separate t...
Страница 5: ...the warranty if unauthorised intervention or action that has not been explicitly approved by us the manufacturer has been carried out In addition the goods must be paid for within the specified payme...
Страница 6: ...tion at the manufacturer The product corresponds to Directive 2011 65 EU RoHS 2 and does not use any materials containing asbestos The product does not contain any PCB or mercury 4 8 Safety devices He...
Страница 7: ...y required for the pellet elegance 24 The thermal overload protection prevents an uncontrolled increase in temperature and pres sure inside the boiler Functioning At a boiler temperature 95 C the valv...
Страница 8: ...by the boiler allo wing the connected devices heating circuit DHW tank fresh water module etc to access it as requi red This ensures sufficiently long uninterrupted com bustion periods for the boiler...
Страница 9: ...d during combustion is transported by the ash extraction auger 7 to the ash container 8 Airflow The air required for combustion is sucked through the primary air duct 3 into the filling chamber downwa...
Страница 10: ...8 88 Flue gas side Flue gas pipe diameter cm 10 13 Height to centre of flue gas pipe D cm 70 72 Centre of flue gas pipe side A cm 44 47 Capacity of ash container l 16 3 16 3 Flue gas mass flow full lo...
Страница 11: ...and control combined 118 123 125 126 Space heating annual usage etaS 77 80 82 83 Annual emission values CO carbon monoxide mg m 93 103 112 116 NOX nitrogen oxide mg m 140 143 146 145 C Total carbon mg...
Страница 12: ...nection aligned upwards 1 Buffer tank return DHW tank return 2 Buffer tank flow DHW tank flow Pellet suction 3 Heating circuit 1 return 4 Heating circuit 1 flow 5 Heating circuit 2 return 6 Heating ci...
Страница 13: ...changes to the Selection menu 13 5 2 Boiler operating mode 1 Chimney sweep function This function is used to perform the emission mea surements prescribed by law Perform emissions measurement 38 2 STO...
Страница 14: ...r 16 7 Output test boiler CAUTION only to be under taken by qualified personnel 8 Qualified personnel menu 17 2 Button is only visible if a message is active 5 4 1 Required boiler values Abb 2 11 Requ...
Страница 15: ...current level and release times are not considered Prerequisite the boiler must have the status Switched off or Standby Manual filling 4 Pressing the button deactivates the automatic vacuum output i...
Страница 16: ...er lock function If the display is not touched for one minute the user lock is active in the screens Password reset 5 The current password is reset to the value solarfocus Adopt as new password 6 Ente...
Страница 17: ...the customer i e not included in the commissioning service and support activities The following points are helpful for setting up a PC router to control the VNC server which requires know ledge of ne...
Страница 18: ...router and therefore the home network can then be reached using this host name To create a connection with the control a port diversion is required from the external port of the router 1 to the IP ad...
Страница 19: ...larm group 2 receives only operationally relevant messages such as information on faults Status email Set the time at which the status email is sent The automatically generated content of the sta tus...
Страница 20: ...om settings Button is only visible when the Room influence parameter is set to On or Sliding this can be found in the Qualified personnel system parameters 3 General settings 21 4 Heating curve 21 6 1...
Страница 21: ...Buffer difference The burner starts when the tank temperature top falls below the required flow temperature minus the buffer difference Example Current required flow temperature 50 C Buffer differenc...
Страница 22: ...lustration Flow temperature at outside temperature of 15 C 45 C Flow temperature at outside temperature of 15 C 22 C Current outside temperature 5 C In the heating circuit operating mode Heating mode...
Страница 23: ...e value at 7 too hot Reduce temperature value at 7 5 C to 5 C too cold Increase temperature value at 11 too hot Reduce temperature value at 11 5 C to 15 C too cold Increase temperature value at 8 too...
Страница 24: ...C and the DHW tank temperature falls to 10 C Always on The DHW tank charge pump is switched on permanently The pump is controlled taking the parameters Required temperature 1 Minimal tem perature and...
Страница 25: ...regulates the tem perature at which the connected hot water devices receive water to this temperature 8 Recirculation control optional additional function A recirculation line means that domestic hot...
Страница 26: ...available if a temperature sensor is connected for the recircu lation temperature The control takes the recirculation temperature required recirculation temperature into account within the time relea...
Страница 27: ...bottom reaches this value i In order to ensure optimum and efficient use of the buffer tank the difference between these two temperatures should be 15 C 10 Solar system optional additional function Th...
Страница 28: ...pecific ecomanager touch control functions Set the room temperature and heating circuit flow temperature including heating times Hot water programs with one time DHW tank charge Display the solar yiel...
Страница 29: ...ering on the web server The touch display must be registered on the SOLARFOCUS Web server Press the app button Abb 2 40 Continue by pressing Accept Abb 2 41 Note the serial number and PIN Switch the S...
Страница 30: ...inciple only one user may access a system If additional users are to access a system then they must be approved in advance Approve additional users 30 12 6 Use of the mySOLARFOCUS app In the boiler co...
Страница 31: ...ser ver SOLARFOCUS or in the mySOLARFOCUS app 28 After successful online registration of the heating sys tem the weatherman button 1 is displayed in the Selection menu after 2 to 3 hours Abb 2 48 Pre...
Страница 32: ...indicates the delay When 100 is reached the burner starts Solar yield in the room 4 Activate this function only if solar radiation directly influences the heating circuit e g solar radiation through...
Страница 33: ...m buffer cylinder temperature bottom in the buffer tank main menu 100 if the burner has started and the buffer tank is within a release time then the buffer tank is not completely charged The charge r...
Страница 34: ...yearly X Perform emissions mea surement 38 as per regional regulations X 1 You can use the E mail message 18 function to be informed about an upcoming emptying of the ash container see Alarm selectio...
Страница 35: ...s Two ways to start with the boiler cleaning The burner is active Switch the boiler off press the STOP button 13 and leave to cool The boiler is in standby status Press the STOP button 13 and if neces...
Страница 36: ...the combustion chamber for ash Switch the boiler to STOP 13 and leave to cool Open the combustion chamber door and check the combustion chamber for ash deposits remove them if present Abb 2 57 Remove...
Страница 37: ...flue gas pipe Switch the boiler to stop operating mode and leave to cool Loosen the 2 socket head screws 1 on the right side of the boiler Lift the cover up and remove Remove the right hand side pane...
Страница 38: ...e 15 Perform emissions mea surement The emissions measurement at the boiler is a legal requirement and must be performed by qua lified personnel on a regular basis Contact the appropriate chimney swee...
Страница 39: ...anager touch control display each message is saved in the message log 16 Abb 2 60 Information window with message Handling of messages Button 1 Close window change to main screen The message remains a...
Страница 40: ...he ash container is full and must be emptied x 47 Heating boiler maintenance recom mended x 49 Boiler door or ash container is open x No Message SO QP 50 The boiler door is open x 51 Battery in operat...
Страница 41: ...urbine or extraction motor commence operation Blockage in pellet hose Check if possible rectify blockage This may be caused by an excessive dust con tent poor pellet quality 15 Error measured value fe...
Страница 42: ...he boiler is defective and must be replaced 30 Feed blockage The pellet auger is blocked Too many pellets in the filling chamber of the boi ler often as a result of ignition faults due to improper com...
Страница 43: ...l marked as full Low filling level in pellet storage area Check the fill level if necessary cover suction heads with pellets fill the pellet storage area 43 Fault in diverter for suction heads DFSH Th...
Страница 44: ...ble connection 69 Error communicating with the indoor air module This message only appears in conjunction with the optional accessory Indoor air module for indoor air damper see also separate manual D...
Страница 45: ...the tripping could be a faul t defect on the power element s rectifier Check cause replace fuse A spare fuse for F12 can be found at slot F13 fur ther information about the electrical fuses 45 For in...