![SolarEdge StorEdge Solution with Backup Скачать руководство пользователя страница 152](http://html1.mh-extra.com/html/solaredge/storedge-solution-with-backup/storedge-solution-with-backup_installation-manual_1313758152.webp)
SE3800A-US
(1)
SE7600A-US
(1)
Unit
STANDARD COMPLIANCE
Safety
UL1741,UL1741 SA, UL1699B, UL1998, CSA
22.2
Grid Connection Standards
IEEE1547, Rule 21, Rule 14H
Emissions
FCC part15 class B
INSTALLATION SPECIFICATIONS
AC Output (Loads/Grid) conduit
size / AWG range
1” / 14-6 AWG
in/AWG
AC Output (Backup) conduit
size / AWG range
0.75-1” drill guides / 14-6 AWG
in/AWG
AC Input (Auto-transformer)
conduit size / AWG range
0.75-1 ” / 14-6 AWG
in/AWG
DC Input (PV) conduit size /
AWG range
0.75 ” / 14-8 AWG
in/AWG
DC Input (Battery) conduit size /
AWG range
0.75” / 12-10 AWG
in/AWG
Dimensions with Connection
Unit (HxWxD)
37 x 12.5 x 7.2 / 940 x 315 x 184
in / mm
Weight with Connection Unit
58.5 / 26.5
lb / kg
Cooling
Natural convection and internal fan (user
replaceable)
Noise
< 50
dBA
Min - Max Operating
Temperature
-13 to +140 / -25 to +60
°F / °C
Protection Rating
NEMA 3R
(1)These specifications apply to inverters with part numbers SE3800A-USS2XXXXX or SE7600A-USS2XXXXX and
connection unit model number BCU-1PH-USS.
StorEdge Single Phase Inverter with Connection Unit for High Power
Technical Specifications
151
StorEdge Solution with Backup MAN-01-00262-1.5
Содержание StorEdge Solution with Backup
Страница 1: ...Installation Guide StorEdge Solution with Backup For North America Version 1 5...
Страница 40: ...Figure 15 Inverter Covers Chapter 3 Installing the Inverter 39 StorEdge Solution with Backup MAN 01 00262 1 5...
Страница 98: ...Chapter 9 Setting Up Communication to the Monitoring Platform 97 StorEdge Solution with Backup MAN 01 00262 1 5...
Страница 101: ...Figure 34 Internal connectors StorEdge Solution with Backup MAN 01 00262 1 5 100 Communication Connectors...
Страница 141: ...Figure 47 The battery holder StorEdge Solution with Backup MAN 01 00262 1 5 140 9V Battery Replacement...