in the RS485 chain; ensure it is not in contact with other wires. Connect the
grounding wire to the grounding bus-bar in the StorEdge Connection Unit.
NOTE
An additional RS485 port (RS485-Plug-in) is available from
SolarEdge, allowing the creation of RS485 Bus Connection; Refer
to
The following sections describe how to physically connect the RS485 bus and how to
configure the bus.
To connect the RS485 communication bus:
1. Remove the inverter cover as described in
Removing the Inverter Cover on page 45.
2. Remove the seal from one of the openings in communication gland and insert the
wire through the opening.
3. Pull out the 9-pin RS485 terminal block connector, as shown below:
Figure 39: The RS485 terminal block
4. Loosen the screws of pins A(+), B(-), and G on the left of the RS485 terminal block
(RS485-1 or RS485-2).
Chapter 9: Setting Up Communication to the Monitoring Platform
105
StorEdge Solution with Backup MAN-01-00262-1.5
Содержание StorEdge Solution with Backup
Страница 1: ...Installation Guide StorEdge Solution with Backup For North America Version 1 5...
Страница 40: ...Figure 15 Inverter Covers Chapter 3 Installing the Inverter 39 StorEdge Solution with Backup MAN 01 00262 1 5...
Страница 98: ...Chapter 9 Setting Up Communication to the Monitoring Platform 97 StorEdge Solution with Backup MAN 01 00262 1 5...
Страница 101: ...Figure 34 Internal connectors StorEdge Solution with Backup MAN 01 00262 1 5 100 Communication Connectors...
Страница 141: ...Figure 47 The battery holder StorEdge Solution with Backup MAN 01 00262 1 5 140 9V Battery Replacement...