21
SUNSYS pro - SUNSYS station
- Ref.: IOMSUNMOXX00-GB 00
ENGLISH
5. INSTALLATION
The inverter is connected to the photovoltaic generator via the DC terminals, and to the main AC network via the AC power terminals.
• Apply the ring terminals to the cables.
• Remove the panels protecting the connection zone in front of the terminals.
• Fix the protection wire (PE) to the connection terminal.
• Fix the wires (L1, L2, L3) to the connection terminals.
• Fix the wires (L+,L-) to the connection terminals.
• Fix the cables to the cable support guide using cable fastening brackets.
• Reposition the panels protecting the connection zone in front of the terminals.
DANGER!
Risk of electric shock from live device parts!
The inverter can be connected to a maximum of three power supplies:
1 DC cable - Photovoltaic generator power supply (separated for the three modules or shared)
2 AC cable - Power from the mains network, supplied by the electricity company
3 AC cable - Auxiliary power supply
• Before carrying out any work, make sure the electricity supply has been disconnected.
• All DC power supplies should be considered as part of the same circuit, even in the configuration with centralised multi-
string inverter. Before carrying out any work, make sure all electricity supplies have been disconnected.
NOTE
Torque for the DC and AC power terminals: 20 Nm
5.2.
CONNECTING THE PHOTOVOLTAIC GENERATOR AND MAIN AC NETWORK
TO THE POWER TERMINALS OF THE
SUNSYS PRO
R01 INVERTER
L1
L3
PE
L–
L2
L+
5.2-1
Key
PE: Connection terminal for the protective earth wire (PE)
L1, L2, L3: Connection terminals for the main AC network
3N
L+, L-: DC connection terminals for the photovoltaic generator
Ring terminals
Cable fastening brackets