28
SUNSYS pro - SUNSYS station
- Ref.: IOMSUNMOXX00-GB 00
28
SUNSYS pro - SUNSYS station
- Ref.: IOMSUNMOXX00-GB 00
6. OPERATING MODES
NOTE
If the code is not entered, the 'initial startup' procedure cannot be completed and the equipment will be prevented from
operating. When contacting the Service Centre for the activation code, you can obtain detailed information relating to the
services available for the equipment in question, in addition to regular preventive maintenance schedules.
Call the freephone
number
800.00.80.85
Completing the 'initial startup' procedure
The 'initial startup' procedure may only be completed using the confirmation menu option that appears if the activation code has
been entered.
At this point the inverter is activated and ready.
If the IMD permanent isolation controller (optional) is installed, check its configuration via the SERVICE menu. For setting details,
pleaser refer to the sheet supplied with the IMD.
6.2. SWITCHING ON THE INVERTER
Switch on the inverter as follows (Figures 6.3-1, 6.3-2, 6.3-3):
• Set all the DC input Q1 disconnection switches for the modules to position 1.
• Set the inverter AC output Q70 disconnection switch to position 1.
• Set all the AC output Q3 disconnection switches for the modules to position 1.
This procedure is also described in the menu COMMANDS -> Start Procedure.
6.3. SWITCHING OFF THE INVERTER
Switch off the inverter as follows (Figures 6.3-1, 6.3-2, 6.3-3):
• Set all the AC output Q3 disconnection switches for the modules to position 0.
• Set the inverter AC output Q70 disconnection switch to position 0.
• Set all the DC input Q1 disconnection switches for the modules to position 0.
The inverter is now switched off. This procedure is also described in the menu COMMANDS -> Stop Procedure.
If the auxiliary power supply also needs to be cut off, disconnect the cable from the Auxiliary Power Supply Input socket or break
the fuse connection. This procedure will switch off all the auxiliary inverter equipment, including the system controller and the mimic
panel. The general AC power contactor for the machine will also be opened.
DANGER!
Risk of electric shock from live device parts!
The inverter can be connected to a maximum of three power supplies:
1) DC cable - Power from the photovoltaic generator
2) AC cable - Power from the mains network, supplied by the electricity company
3) AC cable - Auxiliary power supply
• Before carrying out any work, make sure the electricity supply has been disconnected.