27
SUNSYS pro - SUNSYS station
- Ref.: IOMSUNMOXX00-GB 00
ENGLISH
6. OPERATING MODES
6.1. ACTIVATING THE INVERTER FOR THE FIRST TIME
The first time the equipment is switched on the system displays the Activation page; a guided procedure follows on the screen. In
particular, when scrolling the menu options it is possible choose the user interface language, set the system configuration and the
country in which the equipment is installed.
System setup
In the system setup menu set the number of modules installed in the cabinet from 1 to 3 depending on the size of the machine (33
kW, 66 kW or 100 kW).
NOTE
All the modules inside the cabinet must be powered in order to successfully complete the configuration procedure. When
following the guided procedure if more than one module is fitted the type of connection on the DC side is required for each.
This can be:
• Stand-Alone if the module in question is connected individually to an array of photovoltaic panels (see figure 2.2-9
Centralised Multi-String Inverter);
• Modular if the module in question is connected in parallel with other modules to the same array of photovoltaic panels
(see figure 2.2-8 Centralised Modular Inverter).
Confirm the settings.
Transformer configuration
When installing the 100 kW system (3 modules) make sure the type of transformer selected in the Transformer Type
menu corresponds to the installed device. The default transformer type 'SOCOMEC (built-in)'; only select 'External' if
the machine is not fitted with a SOCOMEC transformer.
Country Setting
Choosing the country is particularly important, as it leads to the automatic configuration of the inverter in compliance with the stan-
dards in force in that country.
All other parameters appearing in the 'initial startup' guided procedure menu will therefore be configured correctly and will not usually
need to be changed, unless the local electricity supply company has specific requirements which need to be met.
NOTE
The country of installation cannot be changed after the first machine activation. If this becomes necessary, contact an
authorised SOCOMEC service centre.
Call the freephone number
800.00.80.85
NOTE
The installer is responsible for carrying out the procedure in accordance with national standards.
Activation code
During the initial startup procedure the four-digit activation code must be entered:
The activation code is supplied directly by the relevant Service Centre after the equipment serial number is entered, as shown in the
following message, and ENTER is pressed.