MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
7.2 UPS reference table, starting from 0x0010
Address
Acronym
Description
Value
Comments
Length
Number of ASCII char.
0x0010
I000
SERIAL NUMBER
10
20
MSB = first char of
string
0x001A
I001
SOCOMEC REFERENCE
10
20
MSB = first char of
string
0x0024
I002
USER DEVICE
REFERENCE
6
12
MSB = first char of
string
0x002A
I003
USER DEVICE
LOCATION
6
12
MSB = first char of
string
7.3 UPS status table, starting from 0x0030
ITYS PRO STATUS
Generic ad-
dress
Bits
Acronym
Description
0x0030
b00
S000
Load protected by Inverter
OUTPUT STATUS
b01
S001
b02
S002
Load supplied by automatic Bypass
b03
S003
b04
S004
Load OFF
b05
S005
b06
S006
In eco mode
FUNCTIONING MODE
b07
S007
b08
S008
b09
S009
Service Mode
b10
S010
b11
S011
Operating
DEVICE STATUS
b12
S012
Available
b13
S013
On Standby
b14
S014
b15
S015
Maintenance Alert
0x0031
b00
S016
Output Breaker closed
DEVICE ENVIRONMENT
b01
S017
b02
S018
b03
S019
b04
S020
b05
S021
b06
S022
b07
S023
Gen set ON
b08
S024
b09
S025
b10
S026
Automatic Start in progress
PROCEDURES
b11
S027
b12
S028
UPS OFF procedure in progress
b13
S029
b14
S030
b15
S031
Alarm Ack. request