MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
5. MODBUS UPS DATA ACCESS
5.1 Modbus generic table
Generic address
Length (in 16 bits
word)
Table
Description
Type
Access
0x0001
15
CONFIGURATIONS
LIST OF CONFIG
Values
Read
0x0010
10
SERIAL NUMBER
STRING
ASCII
Read
0x001A
10
SOCOMEC REF
SOCOMEC RANGE
NAME
ASCII
Read
0x0024
6
USER DEVICE REF
CUSTOMER REF
ASCII
Read
0x002A
6
USER DEVICE
LOCATION
CUSTOMER LOCATION
ASCII
Read
0x0030
6+2
(for parallel system)
STATUS
UPS STATUS
Bits
Read
0x0038
6+2
(for parallel system)
ALARMS
UPS ALARMS
Bits
Read
0x0040
80
MEASUREMENTS
LIST OF VALUES
Values
Read
0x00C0
7
MEASUR. CTRL MGNT
BIT = 1 = MEAS.
MANAGED
Bits
Read
0x00C7
2
PERMISSONS
BIT = 1 CONTROL
ENABLED
Bits
Read
0x00C9
2
CONTROLS
1 BIT = 1 CONTROL
Bits
Write
0x00CB
4
UPS CLOCK
MSB/LSB FORMAT
Values
Read/
write
Detail of data type:
Values: 1 word = 16 bit integer: value range: 0 to 65535 or -32768 to +32768
format of values is described in the measurements table.
ASCII: 1 word = 2 characters: MSB = 1st character ASCII code, LSB = 2nd character ASCII code
Bits: 1 words = 16 binary info (Status or Alarms) bit = 1 means info ON/YES, 0 = OFF/NO
Bit 0 = 1st data (S000 or A000, according to address)