MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
7.9 UPS CLOCK table, starting from 0x00CB
To send a command bit, write from the 0x00CB to 0x00CE address using as a 'Function' the code '0x10'.
See 'Functions used' and 'Summary of frame format' paragraphs for Modbus frame description.
Generic
address
Acronym
Description
Value
Comments
MSB
LSB
0x00CB
K000
Minutes & Seconds
Minute: 0 - 59
Seconds: 0 - 59
read / write
0x00CC
K001
Day & hours
Day: 1 - 31
Hours: 0-23
read / write
0x00CD
K002
Month & day of the week
Month: 1 - 12
1 = Monday - 7 =
Sunday
read / write
0x00CE
K003
Year
year = value + 2000
read / write