MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
4. MODBUS TCP – IDA interface (MODBUS TCP card)
4.1 Installation of the MODBUS TCP Card
The interface must first be installed in the appropriate slot and
fastened to the com slots using 2 screws.
4.2 Serial connection default setting
Serial connection parameters are set by an auto baud rate
procedure with a timeout of 40 seconds.
4.3 Features and led description
Standard supported:
IEEE 802.3
Mode supported:
10/100Base-T
10/100Mbps (auto sensing)
Half-duplex & Full-duplex mode (auto sensing)
Connector type:
RJ-45
LED type
Color
Meaning
RJ45
Yellow
Line detected
Yellow flashing
Searching line
Off
No Ethernet line
RJ45
Green
ON
Green flashing
MODBUS TCP Traffic
Off
No traffic
Interface LED TX ON
Green
When transmitting data
Interface LED RX ON
Green
When receiving data
5V ISO
NOTE!
Refers to Appendix 1.