41
EN
MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
MASTERYS BC+ & GP4 STATUS
Address
Bits
Acronym
Description
0x0033
b00
S048
Rectifier Input Supply present
RECTIFIER
b01
S049
Rectifier ON
b02
S050
Charger ON
b03
S051
b04
S052
Inverter ON
INVERTER
b05
S053
Inverter Switch ON
b06
S054
b07
S055
b08
S056
Bypass Input Supply present
BYPASS
b09
S057
Bypass Static Switch closed
b10
S058
Bypass Input & Inverter synchronised
b11
S059
b12
S060
POWER SHARE
b13
S061
b14
S062
b15
S063