MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
8.5 UPS status table, starting from 0x0030 or 0x(u)030
MASTERYS BC+ & GP4 STATUS
Address
Bits
Acronym
Description
0x0030
b00
S000
Load protected by Inverter
OUTPUT STATUS
b01
S001
b02
S002
Load supplied by automatic Bypass
b03
S003
Load supplied by Maintenance Bypass
b04
S004
Load OFF
b05
S005
b06
S006
In eco mode
FUNCTIONING MODE
b07
S007
Energy saver
b08
S008
b09
S009
Service Mode
b10
S010
b11
S011
Operating
DEVICE STATUS
b12
S012
Available
b13
S013
On Standby
b14
S014
Isolated
b15
S015
Maintenance Alert
0x0031
b00
S016
Output Breaker closed
DEVICE ENVIRONMENT
b01
S017
External maintenance bypass close
(1)
b02
S018
b03
S019
b04
S020
b05
S021
b06
S022
b07
S023
Gen set ON
b08
S024
b09
S025
b10
S026
Auto-test procedure in progress
PROCEDURES
b11
S027
Maint. Bypass procedure in progress
b12
S028
UPS OFF procedure in progress
b13
S029
b14
S030
b15
S031
Alarm Ack. request
0x0032
b00
S032
Battery OK
BATTERY
b01
S033
Battery charged
b02
S034
Battery Test in progress
b03
S035
Battery Test scheduled
b04
S036
Battery charging
b05
S037
Battery Test interrupted
b06
S038
b07
S039
b08
S040
DC STORAGE SYSTEM
b09
S041
b10
S042
b11
S043
b12
S044
b13
S045
b14
S046
b15
S047
1. If option present