MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
6.8 Module summary table, starting from 0x0036
MODBUS makes it possible to view the module status from the Unit level through following table:
MODULYS GP STATUS
Unit address
Bits
Acronym
Description
0x1036
b00
S096
Module 1 Operating
MODULES
b01
S097
Module 2 Operating
b02
S098
Module 3 Operating
b03
S099
Module 4 Operating
b04
S100
Module 5 Operating
b05
S101
Module 6 Operating
b06
S102
Module 7 Operating
b07
S103
Module 8 Operating
b08
S104
b09
S105
b10
S106
b11
S107
b12
S108
b13
S109
Bypass Operating
b14
S110
b15
S111
0x1037
b00
S112
1 Available
MODULES
b01
S113
2 Available
b02
S114
3 Available
b03
S115
4 Available
b04
S116
5 Available
b05
S117
6 Available
b06
S118
7 Available
b07
S119
8 Available
b08
S120
b09
S121
b10
S122
b11
S123
b12
S124
b13
S125
Bypass Available
b14
S126
b15
S127