30
EN
MODBUS RTU / MODBUS TCP for Modulys GP 2.0 - ITYS PRO UPS - Masterys GP4 UPS - Masterys BC+ UPS range - Ref.: IOMXXXOPXX00-EN 00
7.5 UPS alarms table, starting from 0x0038
ITYS PRO ALARMS
Address
Bits
Acronym
Description
0x0038
b00
A000
Imminent Stop
LOAD
b01
A001
Overload
b02
A002
Ambient Temperature Alarm
b03
A003
Transfer locked
b04
A004
Transfer impossible
b05
A005
b06
A006
b07
A007
b08
A008
MODE
b09
A009
b10
A010
b11
A011
b12
A012
Maintenance Alarm
SERVICE
b13
A013
Remote Service Alarm
b14
A014
Remote Service Preventive Alarm
b15
A015
General Alarm
0x0039
b00
A016
Battery disconnected
BATTERY
b01
A017
Battery discharged
b02
A018
End of Backup Time
b03
A019
Operating on Battery
b04
A020
Battery Temperature Alarm
b05
A021
Battery Room Alarm
b06
A022
Battery Test failed
b07
A023
b08
A024
b09
A025
b10
A026
b11
A027
Battery Alarm
b12
A028
b13
A029
DC STORAGE
b14
A030
b15
A031
0x003A
b00
A032
Rectifier Critical Alarm
RECTIFIER
b01
A033
Rectifier Preventive Alarm
b02
A034
b03
A035
Rectifier Input Supply not OK
b04
A036
Gen Set Alarm
b05
A037
Charger Critical Alarm
b06
A038
Charger Preventive Alarm
b07
A039
b08
A040
Inverter Critical Alarm
INVERTER
b09
A041
Inverter Preventive Alarm
b10
A042
b11
A043
Imminent redundancy lost
b12
A044
b13
A045
b14
A046
b15
A047