52
EN
ISOM DIGIWARE - 546780C - SOCOMEC
8 .1 .2 . F-60
1
2
3
4
5
6
ON
FAULT
COM
TEST
RESET
ALARM
F-60
ISOM
Power supply (green)
Alarm channels 1 to 6
(amber)
System fault (red)
Communication (amber)
Addressing button in
config mode
Test (long press) / Reset
(short press) in operating
mode
LED state
Fixed
Blinking
Pulse
ON
In operation
The screen communicates with
the device to retrieve the values/
data to display.
10 seconds – on request via a
Modbus command to identify the
device (remote screen…)
1 second to start-up
FAULT
An alarm (logical/analogue) is
active (does not take priority if
there is a setup alarm at the same
time)
At least one setup alarm is active
(current sensor disconnected, V/I
not compatible)
1 second to start-up
COM
Addressing problem.
Address OK
1 second to start-up and when a
frame received is processed
/ALARM
At least one of the 6 channels is
showing an insulation fault (the
LED(s) for the faulty channels are
also constantly on)
Presence of a saturation current
(the LED(s) for the faulty channels
are flashing) or the measuring
system is blinded
Problem connecting the locating
core balance transformer or the
T-15
Manual test in progress
8 .1 .3 . T-15
ISOM T-15
Insulation alarm (amber)
LED state
Fixed
Blinking
Pulse
/ALARM
Presence of an insulation fault
on the remote device monitored
by the connected core balance
transformer
Problem with connecting to the
core balance transformer or the
measuring system is blinded