45
EN
ISOM DIGIWARE - 546780C - SOCOMEC
Continuous current - 6 circuits
DC / IMD + FLD
L-60
KE L1
FE
L2
L+
L-
1
F-60
I04
I05
I06
I01
I02
I03
M
M
M
M
M
M
Note relating to connections:
The Easy Config software can also be used to select numerous other configuration variants for the types of loads and
associated network voltages. (see section 10.1.2.2.)
6 .3 .3 . Coupled networks
6.3.3.1. Simple coupled networks without fault-locating options
In the case of coupled networks, you must ensure that only one IMD is active. You can do this by setting and using
I/O configurations for the ISOM Digiware L-60 (see section 10.1.2.4 on how to configure I/O in "disconnection"
mode).
Principle diagram:
Digiware
Digiware
Exclusion IMD
NOTE: Some applications may require you to manage the positions of general cut-off devices of the 2 transformers,
as part of excluding the IMD.
6.3.3.2. Simple coupled networks with fault-locating options
When using fault location on coupled networks, the operability of the IMD ISOM Digiware L-60 must be guaranteed
so it remains active with the whole set of ISOM Digiware F-60 locating devices.
This management is made possible by the 2 ISOM Digiware systems communicating with one another via an inter-
screen Ethernet communication D-X5.