6.2. Connecting the current sensors
6 .2 .1 . Connection concept
ISOM Digiware F-60
Current sensors TE/TR/TF
or locating core balance
transformers ΔIP
STAGE 2
1
2
STAGE 1
Important:
•
To connect the current sensors or locating core balance transformers, use SOCOMEC cables or equivalent only,
RJ12 straight cables, twisted pair, unshielded, 600 V -10 degC / +70degC in accordance with IEC 61010-1
version 3.0.
•
We recommend that current sensors are installed in the same direction.
•
Always connect input I01 first.
•
In the same order as inputs I01 to I06, start by cabling the locating core balance transformers, followed by the
current sensors.