ATyS g M - 542933D - SOCOMEC
53
EN
SYMPTOMS
ACTIONS TO BE CARRIED OUT
EXPECTED RESULTS
The product cannot
be switched over
using the handle
Check the direction of rotation of the handle:
• Manual switchover from position 1 to position 2 is executed clockwise.
• The return operation is executed anti-clockwise
The product can be
switched over using the
handle
Check that the product is not padlocked
Use the handle extension on the ALLEN key to check that the appropriate
adjustment torque is applied.
When using a single AC, check that the length of the screws used is not
greater than 20 mm
AUTOMATIC mode
is not activated even
though the cover is
closed
Check that the plastic pin is in place on the bottom of the cover.This pin
activates the sensor which indicates the position of the cover (open or
closed).
The "AUT" LED is lit
Check that automatic operation has not been inhibited by external control
commands (terminals 207-210)
The product cannot
be locked
Check the mechanical position of the changeover switch:
• Locking is only possible in position 0 as standard
• Locking in positions 1-0-2 is possible by modifying the product in
accordance with the instructions
Locking is possible
The product is faulty
Check status of contact 63-64 (Product available):
• Product available: 63-64 = closed
Product non available :
63-64 = open
Product available = A product which is within voltage and frequency limits
without any internal failure.
FAULT LED is OFF
Open and close the cover to reset the fault;
If the product is still faulty
Product must be
returned to factory for
troubleshooting