ATyS g M - 542933D - SOCOMEC
37
EN
13.4. Programming
Whilst in manual mode check the wiring and installation. If ok power up the product.
This product must always be put into service by qualified and approved personal.
The LED signalling is only active when the product supply is on (supply LED lit).
To set the dip switches, it is necessary to open the AUTO/MANU cover.
The commissioning must always result in having at least 1 LED source available lit.
Therefore, the voltage and frequency must be within the defined thresholds.
Any action on the potentiometers changes the settings, even if the cover is closed.
13.4.1. Single phase versionw
A
Dip switch settings
B
Hysteresis settings
C
Timer settings
D
Source supply voltage
and frequency
Auto-Configurationsettings
Stop in 0 position: E-F
E: No stop in O position
F: 2s stop in O position
Type of application: G-H
G: Network - Genset
H: Network - Network
HYST: 20 %ΔU/F
ΔU: 5-20%
ΔF: 3-10%
Loss of priority source timer
FT
FT: 0-60 sec.
U/F
[HYST]
[HYST]
Return of priority source timer
RT
RT: 0-30 min.
U/F
Ensure that the supply
voltage is available and
within the following
limits:
Un: 176-288VAC
Fn: 45-65Hz
Press PROG for ≥ 2s
LED state
Auto Conf
result
Action
Steady ON
OK
Ready
Blinking
Not OK
Repeat step D
E
LED info
Source availability LED
Source
LED ON
LED OFF
LED blinking
Source 1 available Source 1 not available
or out of range
- a timer is counting down
- test mode
Source 2 available Source 2 not available
or out of range
- a timer is counting down
Fault and state of the product LED's
LED ON
LED OFF
LED blinking
Fault
Product OK or
S1-S2 not available
Please wait
Auto mode
Manual mode
Manual retransfer
Fault reset