44
EN
13.7.3.
Mode 2b: Controlled transfer
Network - genset application
•
Contact 207 / 208 closed => Test on load
No
No
No
No
No
No
CDT = cool down timer fixed at 4 min.
Yes
Yes
Yes
Yes
Yes
• Configuration Network - Genset
• Source 1 available
• Product in position I
• Contact 207/208 open or closed
• Contact 207/209 open
Transfert
I -> II
Loss of
genset
Opening of contact
207/209
Transfert
I I -> I
Genset
stop
End of
CDT?
Genset start
order
Closing of
contact 207/209
Genset
available
End of
5s timer ?
End of
5s timer + genset
still available ?
End of 5s timer
+source 1 still
available ?
End of 5s timer
+source 1 still
available ?
Return of
genset