ATyS g M - 542933D - SOCOMEC
18
EN
6.
TECHNICAL DATA
RATINGS
40A
63 A
80 A
100 A
125 A
160 A
Frequencies
50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Thermal current Ith at 40 °C (A)
40
63
80
100
125
160
Thermal current Ith at 50 °C (A)
40
63
80
100
110*
125
Thermal current Ith at 60 °C (A)
40
50
63
80
100*
125
Thermal current Ith at 70 °C (A)
40
40
50
63
80*
100
Rated assigned insulation voltage Ui (V) (Power circuit)
800
800
800
800
800
800
Rated impulse withstand voltage Uimp (kV) (power circuit)
6
6
6
6
6
6
Rated insulation voltage Ui (V) (control circuit)
300
300
300
300
300
300
Rated impulse withstand voltage Uimp (kV) (control circuit)
2.5
2.5
2.5
2.5
2.5
2.5
Rated operational currents
(A)
IEC 60947-3 at 415 VAC at
40 °C
AC 21A / 21 B
40/40
63/63
80/80
100/100
125/125
160/160
AC 22A / 22 B
40/40
63/63
80/80
100/100
125/125
125/160
AC 23A / 23 B
40/40
63/63
80/80
100/100
125/125
125/160
Rated operational currents
(A) IEC 60947-6-1 415Vac
at 40 °C
AC 33B / AC32B
**AC 33iB
40/40
63/63
80/80
100/100
125/125 125**/160
Fuse protected short-circuit
withstand if using gG DIN
fuses
Fuse protected short-circuit
withstand (kA eff)
50
50
50
50
50
40
Associated fuses (gG DIN)
40
63
80
100
125
160
Short-circuit capacity
Rated short-term withstand
current: Icw 1s (kA eff)
4
4
4
4
4
4
Rated short-term withstand
current: Icw 30ms (kA eff)
10
10
10
10
10
10
Switching time at In
excluding loss of supply
sensing time and excluding
any delay timers applicable.
I-II or II-I (ms)
180
180
180
180
180
180
Duration of “electrical
blackout” at Un (ms)
90
90
90
90
90
90
I-O / O-I / II-O / O-II (ms)
45
45
45
45
45
45
Consumption
Inrush current(A)
20
20
20
20
20
20
Consumption in stabilised
state (VA)
6
6
6
6
6
6
Mechanical characteristics
Number of changeovers
10000
10000
10000
10000
10000
10000
Connection cross-section
( not compatible with
aluminium cables)
Minimum size (Cu mm²),
flexible and rigid
10
10
10
10
10
10
Maximum size (Cu mm²),
flexible and rigid
70
70
70
70
70
70
Equipment class (According to IEC 60947-6-1)
PC
PC
PC
PC
PC
PC
EMC environment
A
A
A
A
A
A
* Possibility of reaching 125A with bigger connection cross-sections and use of the 160A bridging bar.
** AC 33iB 160A according to GB 14048.11.
This is a class A product. In a domestic environment, this product may cause radio interference in which
case the user may be required to take adequate measures.
Содержание ATyS g M
Страница 1: ...Automatic Transfer Switching Equipment ATyS g M INSTALLATION AND OPERATING MANUAL EN...
Страница 11: ...ATyS g M 542933D SOCOMEC 11 EN...
Страница 15: ...ATyS g M 542933D SOCOMEC 15 EN...
Страница 54: ...542933D CORPORATE HQ CONTACT SOCOMEC SAS 1 4 RUE DE WESTHOUSE 67235 BENFELD FRANCE www socomec com...